To switch to your Data Protocol and use it for communication: Configure parameter
"Modbus protocol number" to your customer specific protocol number and reboot
the control.
Summary: The self-mappable address range is defined with a protocol number from
65100 to 65199 and has a maximum length of 300 addresses. Communication using
customer specific data protocols is configurable similar to other already existing protocols
5003, 5011 etc. Navigate to [Parameter / Configuration / Configure interfaces / Modbus
protocol].
6.5.4.3
Status/diagnostic Modbus Telegram Mapper
The easYgen provides an information whether the Modbus TelegramMapper mapping file
could be successful parsed and interpreted. Navigate to [STATUS MENU / Interfaces /
>Ethernet / Modbus TCP/IP] to get an error code.
Fig. 326:
Status Modbus mapping table error
Modbus: Mapping table error (12259):
Error codes:
• 0: No error
•
• error line: There is a syntax error -- for any misformatted line
•
• 200000: File not found -- when file corresponding to selected protocol does not exist
•
• 300000: Too complex command discovered
•
• 700000: Too many analog/logic manager indices (i.e. > 32)
•
• 800000: Memory for the table exhausted (file too big)
•
819
easYgen-3000XT Series
B37574
6 Application Field
6.5.4.3 Status/diagnostic Modbus Telegram Mapper