ID
Parameter
CL
Setting range
[Default]
Description
to the rules for Delta connected
systems.
Monitoring refers to the following
voltages:
• VL12, VL23, VL31
•
[3Ph 4W]
Measurement is performed Line-
Neutral (WYE connected system)
and Line-Line (Delta connected
system). The protection depends
on the setting of parameter
.
Phase voltages and the neutral
must be connected for proper
calculation. Measurement, display
and protection are adjusted
according to the rules for WYE
connected systems.
Monitoring refers to the following
voltages:
• VL12, VL23 and VL31
•
(parameter
configured to "Phase-phase")
• VL1N, VL2N and VL3N
•
(parameter
configured to "Phase-
neutral")
Notes
If this parameter is configured to
1Ph 3W, the generator and mains
rated voltages (parameters
) must be
entered as Line-Line (Delta) and
the busbar 1 rated voltage
(parameter
entered as Line-Neutral (WYE).
For information on measuring
principles refer to
1850
Generator current
measuring
2
[L1 L2 L3]
All three phases are monitored.
Measurement, display and
protection are adjusted according
to the rules for 3-phase
measurement. Monitoring refers
to the following currents: IL1, IL2,
IL3
Phase L1
Phase L2
Phase L3
Only one phase is monitored.
Measurement, display and
protection are adjusted according
to the rules for single-phase
measurement.
Monitoring refers to the selected
phase.
Notes
This parameter is only effective if
generator voltage measuring
590
easYgen-3000XT Series
B37574
4 Configuration
4.6.2 Generator
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...