ID
Parameter
CL
Setting range
[Default]
Description
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
1945
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32: 96.{xx} LM:
Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE. Example: 96.01 LM: Flag 1,
96.02 LM: Flag 2, ..., 96.32 LM:
Flag 32
4.5.4.8
Configure Neutral Contactor
General notes
The monitoring of the Neutral Contactor (NC) feedback "17.09 N-cont. reply mism." is
performed always, if the Neutral Interlocking (parameter
function are enabled (parameter
). The monitor checks, if the feedback behaves
according to the NC command. With a configurable delay time, the alarm is activated with
a general alarm text. Open failure or closure failure are not differentiated.
Please refer to
╚═▷ “6.3.14 Neutral Interlocking”
ID
Parameter
CL
Setting range
[Default]
Description
5148
Monitoring
2
On
Monitoring of the Neutral
Contactor is carried out according
to the following parameters, if the
Neutral Interlocking function
(parameter
[Off]
Monitoring is disabled.
5152
Delay
2
0.10 to 5.00 s
[2.00 s]
Period of continuous failure signal
before tripping a failure.
5149
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
This function may be assigned an
independent alarm class that
specifies what action should be
taken when this function triggers
an alarm.
Notes
For additional information refer to
.
548
easYgen-3000XT Series
B37574
4 Configuration
4.5.4.8 Configure Neutral Contactor
Released