Firing speed and delayed monitoring
When the firing speed is reached, the starter is disengaged under one of the following
conditions:
• The measurement via MPU is enabled (On):
•
◦ Ignition speed measured via MPU is detected or
◦
◦ Ignition speed measured via the generator voltage is detected or
◦
◦ Ignition speed measured via ECU/J1939 or
◦
◦ Conditions for "Ignition speed" (see LogicsManager) equal true.
◦
• The measurement via MPU is disabled (Off):
•
◦ Ignition speed measured via the generator voltage is detected or
◦
◦ Conditions for "Ignition speed" (see LogicsManager) equal true.
◦
Fig. 149:
Engine - firing speed
Auxiliary operations
The auxiliary operations start, as soon as the engine is to be started or a running engine
is detected.
At the same time, the discrete output for the auxiliary services (LogicsManager 03.01) will
be enabled. This discrete output remains enabled as long as speed is detected or if the
controller is in the MANUAL mode.
216
easYgen-3000XT Series
B37574
4 Configuration
4.4.1.2 Engine Start/Stop
Released