ID
Parameter
CL
Setting range
[Default]
Description
df/dtdf/dt
df/dt monitoring is carried out
according to the parameters
described in
Ph-shift,df/dt
Phase shift monitoring and df/dt
monitoring is carried out. Tripping
occurs if phase shift or df/dt is
triggered.
3053
Monitoring
2
[1- and 3-phase]
During single-phase voltage
phase/vector shift monitoring,
tripping occurs if the phase/vector
shift exceeds the configured
threshold value (parameter
) in at least one of the three
phases.
3-phase
During three-phase voltage phase/
vector shift monitoring, tripping
occurs only if the phase/vector
shift exceeds the specified
threshold value (parameter
) in all three phases within
2 cycles.
Notes
If a phase/vector shift occurs in
one or two phases, the single-
phase threshold value
(parameter
) is taken
into consideration; if a phase/
vector shift occurs in all three
phases, the three-phase threshold
value (parameter
) is
taken into consideration. Single
phase monitoring is very sensitive
and may lead to nuisance tripping
if the selected phase angle
settings are too small.
3 phase mains phase shift
monitoring is only enabled if
Mains voltage measuring
(parameter
configured to "3Ph 4W" or "3Ph
3W".
3054
Limit 1-phase
2
3 to 30°
[20°]
If the electrical angle of the mains
voltage shifts more than this
configured value in any single
phase, an alarm with the class
configured in parameter
is initiated.
Depending on the configured
mains decoupling procedure
(parameter
MCB, or an external CB will be
opened.
3055
Limit 3-phase
2
3 to 30°
[8°]
If the electrical angle of the mains
voltage shifts more than this
configured value in all three
phases, an alarm with the class
configured in parameter
is initiated.
Depending on the configured
mains decoupling procedure
525
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.12 Change Of Frequency
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...