ID
Parameter
CL
Setting range
[Default]
Description
1746
Mains rated react.
pwr. [kvar]
2
0.5 to 99999.9 kvar
[200.0 kvar]
This value specifies the mains
reactive power rating, which is
used as a reference figure for
related functions.
The mains rated reactive power is
a reference value used by several
monitoring and control
functions(
1785
Mains rated current
2
1 to 32000 A
[300 A]
This value specifies the mains
rated current, which is used as a
reference figure for related
functions.
1853
Mains voltage
measuring
2
[3Ph 4W]
Measurement is performed Line-
Neutral (WYE connected system)
and Line-Line (Delta connected
system). The protection depends
on the setting of parameter
.
Phase voltages and the neutral
must be connected for proper
calculation. Measurement, display
and protection are adjusted
according to the rules for WYE
connected systems.
Monitoring refers to the following
voltages:
• VL12, VL23 and VL31
•
(parameter
configured to "Phase-phase")
• VL1N, VL2N and VL3N
•
(parameter
configured to "Phase-
neutral")
• VL12, VL23, VL31, VL1N,
•
VL2N and VL3N (parameter
3Ph 3W
Measurement is performed Line-
Line (Delta connected system).
Phase voltages must be
connected for proper calculation.
Measurement, display and
protection are adjusted according
to the rules for Delta connected
systems.
Monitoring refers to the following
voltages:
• VL12, VL23, VL31
•
1Ph 2W
Measurement is performed Line-
Neutral (WYE connected system) if
parameter
is configured
to "Phase - neutral" and Line-Line
(Delta connected system) if
parameter
is configured
to "Phase - phase".
Measurement, display and
protection are adjusted according
594
easYgen-3000XT Series
B37574
4 Configuration
4.6.4 Mains
Released