
CAUTION!
Set factory default settings causes easYgen power cycle!
Don't run "Set factory default values"
during controlling a genset because it
causes a power cycle of the easYgen control.
The default values shall be reset.
• Modbus address = 40000 + (Par. ID + 1) = 41702
•
• Modbus length = 1 (UNSIGNED 16)
•
⚙
ᐳ
Fig. 324:
Modscan32 at address 410418
1. ▷
Use the "display options" to set the value format to decimal.
2. ▷
Double-click the address to issue a
Write Register
command.
▶
Fig. 325:
Write register - resetting the default values
shows how the parameter is enabled using the ModScan32 Software. The
value must be set to "1" to enable the parameter.
6.5.3
Exception Responses
The Modbus protocol has multiple exception responses to show that a request could not
be executed. Exception responses can be recognized if the response telegram contains
the request function code with an offset of 128 (0x80 hex).
explains possible reasons for an exception response that occurred.
817
easYgen-3000XT Series
B37574
6 Application Field
6.5.3 Exception Responses
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...