Fig. 213:
Application mode A02 (schematic)
The easYgen requires the feedback reply from GCB and MCB in this application mode.
These replies are used to define, whether the easYgen controls frequency, shares the
load with other gensets or performs active load control.
The following feedback signals and commands are used in this application mode and
fixed to the respective discrete inputs and outputs:
• DI 7 "Reply MCB" (mains parallel)
•
• DI 8 "Reply GCB" (normally closed (break) contact)
•
• DO 7 "Command: GCB open"
•
683
easYgen-3000XT Series
B37574
6 Application Field
6.1.2 Application mode A02 (GCB open)
Released