4.5.6.5
CAN Interface 2
General notes
Fig. 199:
CAN2 state
The CANopen interface 2 is monitored. If the interface does not receive a message from
the external expansion board (Node-ID) before the delay expires, an alarm will be
initiated.
This is indicated in the following menus:
HMI: [Next Page / Diagnostic / Interfaces / CAN / CAN 2 state]
Toolkit: [STATUS MENU / Diagnostic / Interfaces / CAN / CAN 2 state]
If this protective function is triggered, the display indicates "CANopen interface 2" and
the logical command variable "08.19" will be enabled.
If you are not using the exact amount of external I/O modules you have defined, the
monitoring function does not work correctly.
ID
Parameter
CL
Setting range
[Default]
Description
16187
Monitoring
2
On
CANopen interface 2 monitoring is
carried out according to the
following parameters.
[Off]
Monitoring is disabled.
16186
Delay
2
0.01 to 650.00 s
The maximum receiving break is
configured with this parameter.
560
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.5 CAN Interface 2