ID
Parameter
CL
Setting range
[Default]
Description
The alarm class is valid for
parameter
.
For additional information refer to
3293
Self acknowledge
2
[Yes]
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
No
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
Notes
The self acknowledge is valid for
parameter
.
3296
Mains decoupling by
QV
2
On
The QV monitoring function is
linked to the mains decoupling
function with all its consequences
and is assigned to "Delay step 1"
(parameter
[Off]
The QV monitoring function is
ignored in the mains decoupling
function.
4.5.3.12 Change Of Frequency
Phase shift
A vector/phase shift is defined as the sudden variation of the voltage curve which may be
caused by a major generator load change. It usually occurs, if the utility opens the MCB,
which causes a load change for the genset.
The genset control measures the duration of a cycle, where a new measurement is
started with each voltage passing through zero. The measured cycle duration will be
compared with an internal quartz-calibrated reference time to determine the cycle
duration difference of the voltage signal.
The phase shift monitoring is a very sensitive functionality and reacts according to the
settings on each sinus wave constellation.
Please be aware that under special circumstances it may come to a phase shift trip,
when switching elements are taken into the mains measurement lines because mains
voltage sensing lines are switched nearby the genset control.
523
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.12 Change Of Frequency
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...