ID
Parameter
CL
Setting range
[Default]
Description
8892
Show engine speed
2
[Yes]
No
Display of engine speed on home
screen.
8893
AM Engine oil
pressure
2
Determined by AnalogManager
81.25
[A1 = 07.07 100:Engine Oil
Press.] (This default value is a
J1939 value.)
With this AnalogManager the
according oil pressure source can
be configured and scaled. The
indication is displayed in the
format 00.0bar (000psi).
Notes
If »bar« is assigned the unit will be
converted into "psi" automatically
if the corresponding parameter for
conversion
is configured
to YES.
8894
Show engine oil
pressure
2
Yes
[No]
Display of engine oil pressure on
home screen.
8895
AM Engine hours
2
Determined by AnalogManager
81.26
[A1 = 11.55 Eng.oper.hours
[h]]
With this AnalogManager the
according operating hours source
can be configured and scaled. The
indication is displayed in the
format 00000.00h .
8896
Show engine hours
2
[Yes]
No
Display of engine running hours
on home screen.
8897
AM Engine fuel level
2
Determined by AnalogManager
81.27
[A1 = 06.03 Analog input 3]
With this AnalogManager the
according fuel level source can be
configured and scaled. The
indication is displayed in the
format 000.0% .
8898
Show engine fuel
level
2
Yes
[No]
Display of engine fuel level on
home screen.
8899
AM Engine
batt.voltage
2
Determined by AnalogManager
81.28
[A1 = 10.54 Battery voltage
[V]]
With this AnalogManager the
according battery voltage source
can be configured and scaled. The
indication is displayed in the
format 00.0V .
8900
Show engine battery
voltage
2
[Yes]
No
Display of engine battery voltage
on home screen.
8901
AM Engine coolant
temp.
2
Determined by AnalogManager
81.29
[A1 = 07.15 110:Eng.Coolant
Temp.] (This default value is a
J1939 value.)
With this AnalogManager the
according coolant temperature
source can be configured and
scaled. The indication is displayed
in the format 000°C (°F).
Notes
If »°C« is assigned the unit will be
converted into "°F" automatically
if the corresponding parameter for
conversion
is configured
to YES.
175
easYgen-3000XT Series
B37574
4 Configuration
4.3.2.3 Screen configuration
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...