ID
Parameter
CL
Setting range
[Default]
Description
5745
Int. kvar setpoint 1
-99999.9 to +99999.9
[0.0]
This setpoint is active only if PF/
kvar setpoint 1 is set to Mns.
Export kvar or Mns. Import kvar.
5621
Int. power factor
setpoint 2
2
-0.999 to +1.000
[+1.000]
The desired power factor may be
configured here so that the
reactive power is regulated in the
system.
The designations "–" and "+"
stand for inductive/lagging
(generator overexcited) and
capacitive/leading (generator
underexcited) reactive power. This
setpoint is active only in mains
parallel operation.
5746
Int. kvar setpoint 2
-0.999 to +1.000
[0.000]
This setpoint is active only if PF/
kvar setpoint 2 is set to Mns.
Export kvar or Mns. Import kvar.
12921
Setp.2 pwr.factor
2
Determined by LogicsManager
86.84
[(0 & 1) & 1]
= 11913
If this LogicsManager condition is
TRUE, the power factor setpoint 2
will be used instead of power
factor setpoint 1. The power factor
(result of AM)
will be taken into
account.
Notes
For information on the
LogicsManager and its default
settings see
.
5622
React. pwr. ctrl
setpoint ramp
2
0.01 to 100.00 %/s
[3.00 %/s]
The different setpoint values are
supplied to the controller via this
ramp.
The slope of the ramp is used to
alter the rate at which the
controller modifies the setpoint
value. The faster the change in
the setpoint is to be carried out,
the greater the value entered here
must be.
Notes
This ramp is also used in islanded
operation for loading or unloading
an additional genset. An excessive
oscillation may occur if the ramp
is configured too high.
1884
Gen. PF setpoint
filter
2
0.0 to 99.9 s
[0.0 s]
The PT1-filter for the Gen PF or
Gen kvar setpoint mode can be
configured here. The parameter
stands for the 3 times tau value of
a PT1 element. (see drawing).
That means the configured time
defines when 95% of the original
setpoint jump is reached.
Notes
310
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.2 Configure Power Factor / kvar Control