ID
Parameter
CL
Setting range
[Default]
Description
[2.0 s]
configured here in order to
multiply the deadband with the
factor configured in
parameter
Notes
This parameter is only visible if
power factor control
(parameter
configured to "3pos controller".
5791
Max. generator
current
2
0 to 150%
[100%]
This is the maximum generator
current during reactive power
control. The percentage is related
to the rated current setting (ID
5792
Max.react.inductive
pwr.gen.
2
0 to 150%
[80%]
This is the maximum accepted
generator reactive inductive load
(outcome) during reactive power
control at the interchange point.
The percentage is related to the
reactive power setting (ID
).
5793
Max.react.capactive
pwr.gen.
2
0 to 150%
[50%]
This is the maximum accepted
generator reactive capacitive load
(income) during reactive power
control at the interchange point.
The percentage is related to the
reactive power setting (ID
).
5638
AM PF/kvar SP1[-/
kvar]
2
Determined by AnalogManager
81.11
[A1 = 05.10 Intern. PF setp1
[%]]
The power factor / reactive power
setpoint 1 source can be selected
from the available data sources.
The internal “05.10 Intern. PF
setp1 [%]” can be changed
manually at the setpoint screen of
the display.
5639
AM PF/kvar SP2[-/
kvar]
2
Determined by AnalogManager
81.05
[A1 = 05.11 Intern. PF setp2
[%]]
The power factor / reactive power
setpoint 2 source can be selected
from the available data sources.
The internal “05.11 Intern. PF
setp2 [%]” can be changed
manually at the setpoint screen of
the display.
5743
PF/kvar setpoint 1
mode
[Gen.PF]
Mns.Export kvar
Mns.Import kvar
Mains PF
Gen.kvar
Determination of the reactive
power control argument (Modes)
Gen.PF: The value entered as PF/
kvar setpoint is a generator power
factor setpoint.
Mns.Export kvar: The value
entered as PF/kvar setpoint is a
mains export power setpoint in
kvar. Note: Even the value is also
configurable as negative value do
not enter a negative value in this
mode.
Mns.Import kvar: The value
entered as PF/kvar setpoint is a
mains import power setpoint in
308
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.2 Configure Power Factor / kvar Control