ID
Parameter
CL
Setting range
[Default]
Description
1754
Generator rated
current
2
1 to 32000 A
[300 A]
This value specifies the generator
rated current, which is used as a
reference figure for related
functions.
1851
Generator voltage
measuring
2
3Ph 4W OD
Measurement is performed Line-
Neutral (Open Delta connected
system). The voltage is connected
via transformer with 3 Wire.
Phase voltages and the neutral
must be connected for proper
calculation.
Measurement, display and
protection are adjusted according
to the rules for Open Delta
connected systems.
Monitoring refers to the following
voltages:
• VL12, VL23 and VL31
•
1Ph 3W
Measurement is performed Line-
Neutral (WYE connected system)
and Line-Line (Delta connected
system). The protection depends
on the setting of parameter
.
Measurement, display, and
protection are adjusted according
to the rules for single-phase
systems.
Monitoring refers to the following
voltages:
•
configured to "Phase-phase")
• VL1N, VL3N (parameter
•
configured to "Phase-
neutral")
1Ph 2W
Measurement is performed Line-
Neutral (WYE connected system) if
parameter
is configured
to "Phase - neutral" and Line-Line
(Delta connected system) if
parameter
is configured
to "Phase - phase".
Measurement, display and
protection are adjusted according
to the rules for phase-phase
systems.
Monitoring refers to the following
voltages:
• VL1N, VL12
•
3Ph 3W
Measurement is performed Line-
Line (Delta connected system).
Phase voltages must be
connected for proper calculation.
Measurement, display and
protection are adjusted according
589
easYgen-3000XT Series
B37574
4 Configuration
4.6.2 Generator
Released