ID
Parameter
CL
Setting range
[Default]
Description
2211
2217
2205: [30.00 s]
2211: [1.00 s]
2217: [0.40 s]
the delay time configured here, an
alarm will be issued.
Notes
If the monitored generator current
falls below the threshold (minus
the hysteresis) before the delay
expires the time will be reset.
2224
2225
2226
Voltage restraint
monitoring
4
Yes
The control provides voltage
restrained overcurrent relay
according to ANSI 51 V
individually for each generator
current monitoring function.
For details refer to
Generator Voltage Restrained
Overcurrent Monitoring - ANSI
#51V”
.
[No]
Voltage restrained monitoring is
disabled.
2201
2207
2213
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
2201: [Class E]
2207: [Class F]
2213: [Class F]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
2202
2208
2214
Self acknowledge
2
4
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
2203
2209
2215
Enabled
4
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
434
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.4.1 Generator Time-Overcurrent (Level 1, 2 & 3) ANSI# 50/51
Released