HMI Text
Note
04.66 Mains failure ended
TRUE if "Mains Settling Time" is triggered OR mains frequency dependent power
up-/derating becomes deactive.
Reset if
power setpoint after resynchronization is reached OR
GCB is opened OR
mains is ok again for the time cofigured with parameter 5015.
04.67 Reserve power avail.
TRUE if reserve power is available.
04.68 ATS start request
TRUE if LDSS with predicted load wants to start the engines. This command
variable
can be assigned to the LM "Start request in
AUTO"
04.69 Inhibit ATS
TRUE if "04.68 ATS start request"
is true and the rated power on the bus bar is
lower than the predicted load. It shall be passed to a relay to inhibit the ATS
control to switch load in any direction.
04.70 Opening GCB active
TRUE if the GCB is to be opened. (Independent of the relay NC/NO.)
04.74 PV load ref. 0%
TRUE if the PV inverter shall be limited to 0 % of rated.
04.75 PV load ref. 30%
TRUE if the PV inverter shall be limited to 30 % of rated.
04.76 PV load ref. 60%
TRUE if the PV inverter shall be limited to 60 % of rated.
04.77 PV load ref. 100%
TRUE if the PV inverter shall provide up to 100 % of rated.
9.3.2.5
Group 05: Engine related alarms
TRUE if the alarm is active or latched.
HMI Text
Note
05.01 Overspeed 1
Engine Over speed threshold 1
05.02 Overspeed 2
Engine Over speed threshold 2
05.03 Underspeed 1
Engine Under speed threshold 1
05.04 Underspeed 2
Engine Under speed threshold 2
05.05 Unintended stop
Unintended shutdown
05.06 Eng. stop malfunct.
Shutdown malfunction
05.07 Speed/freq. mismatch
Pickup speed / Frequeny mismatch
05.08 Start fail
Start failure
05.09 Maint. days exceeded
Maintenance days exceeded
05.10 Maint. hrs exceeded
Maintenance hours exceeded
05.11 Charge alt. low volt
Charge Alternator D+ low voltage
05.13 Red stop lamp
ECU red stop lamp
05.14 Amber warning lamp
ECU amber/yellow stop lamp
1092
easYgen-3000XT Series
B37574
9 Appendix
9.3.2.5 Group 05: Engine related alarms