Fig. 333:
Visualization configurations
Data Format(s)
Modbus registers are read and written according to the Modbus standard as Big-endian.
Composite data types like LOGMAN, ANALOGMANAGER, and TEXT use separate
descriptions.
Configuration
The Modbus interface can be used to read/write parameters. According the Modbus
addressing range for the configuration addresses, the range starts at 40001 and ends at
450000. You can always access only one parameter of the system in this address range.
The Modbus address can be calculated depending on the parameter ID as illustrated
below:
Parameter ID < 10,000
Parameter ID >= 10,000
Modbus address =
40000 + (Par. ID+1)
(Par. ID+1)
Table 130: Address calculation
Block reads in this address range depend on the data type of the parameter. This makes
it important to set the correct length in Modbus registers which depends on the data type
(UNSIGNED 8, INTEGER 16, etc.).
Types
Modbus
registers
Remarks
UNSIGNED 8
1
UNSIGNED 16
1
INTEGER 16
1
UNSIGNED 32
2
INTEGER 32
2
LOGMAN
7
Little-endian is used for LogicsManager to be compatible
with (non-XT) easYgen series
845
easYgen-3000XT Series
B37574
7 Interfaces And Protocols
7.6 Modbus Protocol
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...