ID
Parameter
CL
Setting range
[Default]
Description
Off
Monitoring is disabled for Level 1
limit and/or Level 2 limit.
1904
1910
Limit
2
50.0 to 140.0%
1904: [110.0%]
1910: [115.0%]
(Hysteresis: 0.05 Hz)
(Reset Delay: 80 ms)
The percentage values that are to
be monitored for each threshold
limit are defined here.
If this value is reached or
exceeded for at least the delay
time without interruption, the
action specified by the alarm class
is initiated.
Notes
This value refers to the System
rated frequency (parameter
).
1905
1911
Delay
2
0.02 to 99.99 s
1905: [1.50 s]
1911: [0.30 s]
If the monitored generator
frequency value exceeds the
threshold value for the delay time
configured here, an alarm will be
issued.
Notes
If the monitored generator
frequency falls below the
threshold (minus the hysteresis)
before the delay expires the time
will be reset.
1901
1907
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
1901: [Class B]
1907: [Class F]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
1902
1908
Self acknowledge
2
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
1903
1909
Enabled
4
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
430
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.3.2 Generator Overfrequency (Level 1 & 2) ANSI# 81O
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...