ID
Parameter
CL
Setting range
[Default]
Description
output "External
acknowledgment" (via a discrete
input or via an interface).
1940
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32: 96.{xx} LM:
Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE. Example: 96.01 LM: Flag 1,
96.02 LM: Flag 2, ..., 96.32 LM:
Flag 32
4.5.4.7
MCB plausibility
If breaker mode GCB/MCB is configured, this alarm trips (according to the monitor
settings) if the number of closed MCBs is different to the number of easYgen devices in
the same segment.
ID
Parameter
CL
Setting range
[Default]
Description
1941
Monitoring
2
[Off]
Monitoring is disabled.
On
Monitoring of the MCB plausibility
is carried out according to the
following parameters.
1942
Delay
2
0.02 to 99.90 s
[0.20 s]
If the conditions are fulfilled for
this time the alarm "MCB
plausibility" will trip and the
command variable 08.48 becomes
active.
1943
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
An alarm can be assigned that
specifies what action should be
taken when the conditions are
fulfilled.
Notes
For additional information refer to
1944
Self acknowledge
2
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
547
easYgen-3000XT Series
B37574
4 Configuration
4.5.4.7 MCB plausibility
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...