ID
Parameter
CL
Setting range
[Default]
Description
acknowledgment" (via a discrete
input or via an interface).
1918
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.6.10 J1939 Interface - Emission/Malfunction Alarm
General notes
This monitor monitors, whether a specific alarm bit is received from the CAN J1939
interface. This enables to configure the easYgen in a way that a reaction is caused by this
bit (e.g. warning, shutdown).
If this protective function is triggered, the display indicates "Emission lamp DM1" and the
logical command variable "03.45" will be enabled.
ID
Parameter
CL
Setting range
[Default]
Description
1919
Monitoring
2
On
Monitoring of the Emission
Warning Lamp message from the
ECU is carried out according to the
following parameters.
[Off]
Monitoring is disabled.
1920
Delay
2
0 to 999 s
[2 s]
The Emission warning lamp delay
is configured with this parameter.
If the ECU sends the Emission
Warning Lamp On message, the
action specified by the alarm class
is initiated after the delay
configured here expires.
1921
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class A]
An alarm can be assigned, that
specifies what action should be
taken when the conditions are
fulfilled.
Notes
570
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.10 J1939 Interface - Emission/Malfunction Alarm
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...