After energizing the easYgen, a delay is started, which allows a possible "Missing
easYgen" alarm to become active.
When using only CAN, the delay for the first 140 seconds after booting depends on the
Device Number (parameter
): Delay = (Device 11) seconds
This delay serves for detecting the Master of the CAN bus connection. Approximately two
minutes after energizing the easYgen, the alarm delay will be set to a fix time, which
depends on the setting of parameter
(Transfer rate LS fast message) and is in
the range between 3 to 12 seconds.
If load share is with any Ethernet, after energizing the easYgen the delay is 12 s.
After 12 seconds the delay time is approximately 1 s.
During »System update« the alarm is disabled.
For more information see
╚═▷ “6.2.2 Communication Management”
ID
Parameter
CL
Setting range
[Default]
Description
4060
Monitoring
2
On
Multi-unit missing members
monitoring is carried out.
[Off]
Monitoring is disabled.
4061
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
This function may be assigned an
independent alarm class that
specifies what action should be
taken when this function triggers
an alarm.
Notes
For additional information refer to
.
4062
Self acknowledge
2
Yes
The control automatically clears
the alarm if the fault condition is
no longer detected.
[No]
The control does not automatically
reset the alarm when the fault
condition is no longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
4.5.6.18 Multi-Unit System Update
General notes
The multi-unit system update monitoring function checks whether only the participating
units are available (sending data on the load share line).
If the number of available easYgen units is more than the number of displayed "Monitored
easYgen"
580
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.18 Multi-Unit System Update