
feed-in power to stabilize mains. Ripple control is one form of power limitation and is used
in many countries around the world.
Functionality
The energy supply company provides a signal to the ripple control receiver to reduce the
feed-in power of the generating plant. The ripple control receiver switches four relay
contacts according to the required energy power level. This relay contacts correspond for
example to the following energy power levels:
• 100% (full feed-in) - Step 1
•
• 60% - Step 2
•
• 30% - Step 3
•
• 0% (no feed-in) - Step 4
•
The respective contact is closed for the duration of the reduction.
The reduction of the feed-in power must be established within a certain time frame
(depending on national regulations).
Derating of power
The power reduction is realized by using the LogicsManager "Free derating" (parameter
). This function is using an analog signal. For this reason the relay outputs of
the ripple control receiver must be converted into a corresponding analog signal. We
recommend a resistor array like shown in
to convert the relay outputs into a
analog signal (0 to 500 Ohms).
Fig. 265:
Ripple control receiver wiring
R1 =
500 Ohms (or 560 parallel 4.7 k)
R2 =
300 Ohms (or 330 parallel 3.3 k)
R3 =
150 Ohms
744
easYgen-3000XT Series
B37574
6 Application Field
6.3.13 Ripple Control Receiver
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...