ID
Parameter
CL
Setting range
[Default]
Description
values may be configured
independent from each other.
Off
Monitoring is disabled for Level 1
limit and/or Level 2 limit.
2329
2335
Limit
2
-0.999 to 1.000
2329 [+ 0.900]
2335: [+ 0.700]
(Hysteresis: 0.02%)
(Reset Delay: 80 ms)
The values that are to be
monitored for each threshold limit
are defined here.
Notes
If the power factor becomes more
lagging (i.e. inductive,
) than a lagging PF value
(positive) or a leading PF value
(negative) for at least the delay
time (parameters
or
) without interruption,
the action specified by the alarm
class is initiated.
2330
2336
Delay
2
0.02 to 99.99 s
2330: [30.00 s]
2336: [10.00 s]
If the monitored generator power
factor is more lagging than the
configured limit for the delay time
configured here, an alarm will be
issued.
Notes
If the monitored generator power
factor returns within the limit
before the delay expires the time
will be reset.
2326
2332
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
2326: [Class B]
2332: [Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
2327
2333
Self acknowledge
2
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
2328
2334
Enabled
2
Always
Monitoring for this fault condition
is continuously enabled.
[87.70 LM:Eng.mon]
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
456
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.6.1.1 Generator Lagging Power Factor (Level 1 & 2)
Released