6.3.5.1
Operating Modes
Two operating modes may be used with remote control:
• AUTOMATIC
•
• STOP
•
It is possible to fix the operating mode using the LogicsManager function "86.16 LM:
Operat. mode AUTO" (parameter
).
AUTOMATIC
⚙
1. ▷
Fig. 232:
LogicsManager function "Operat. mode AUTO"
The LogicsManager function ""Operat. mode AUTO"" (parameter
) can be
configured as shown in (
).
▶
AUTOMATIC operation mode is always enabled.
If an alarm of alarm class C through F occurs in AUTOMATIC operating mode, the control
does not return to STOP operating mode. If the alarm is cleared after Acknowledgment a
restart is initiated.
It is also possible to configure a discrete input for controlling the operating mode using
the LogicsManager function "86.16 LM: Operat. mode AUTO" (parameter
"86.18 LM: Operat. mode STOP" (parameter
).
⚙
1. ▷
Fig. 233:
LogicsManager function ""Operat. mode AUTO""
The LogicsManager function ""Operat. mode AUTO"" (parameter
) can be
configured as shown in (
).
▶
AUTOMATIC operation mode is enabled as soon as discrete input 9 is energized.
711
easYgen-3000XT Series
B37574