If this protective function is triggered, the display indicates "Start fail" and the logical
command variable "05.08" will be enabled.
ID
Parameter
CL
Setting range
[Default]
Description
3303
Monitoring
4
[On]
Monitoring of the start sequence
is carried out according to the
following parameters.
Off
Monitoring is disabled.
3304
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class F]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
3305
Self acknowledge
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
4.5.2.5
Engine Shutdown Malfunction
General notes
If it is not possible to stop the engine within a configured time, an alarm will be initiated.
If this protective function is triggered, the display indicates "Eng. stop malfunct." and the
logical command variable "05.06" will be enabled.
We recommend to assign this monitoring function to a discrete output to be able to
shutdown the engine with an external device to provide a shutdown redundancy.
474
easYgen-3000XT Series
B37574
4 Configuration
4.5.2.5 Engine Shutdown Malfunction
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...