ID
Parameter
CL
Setting range
[Default]
Description
Notes
Measured values 181
'Ph.ang.busb1-gen.L12' and 184
'Ph.ang.mns.busb1 L12' are not
changed but the compensated
(
) values are taken for
synchronization control and
synchroscope display.
[Off]
The compensation is inactive. The
phase angle is directly taken from
the measurement.
Notes
WARNING: Ensure the following
parameters are configured
correctly to prevent erroneous
synchronization settings. Incorrect
wiring of the system cannot be
compensated for with this
parameter!
Please check during initial
commissioning the phase angle
and the synchronization with a
zero voltmeter.
Recommendation: For safety
reasons, please mark the easYgen
with a label showing the
configured phase angle
compensation.
8824
Phase angle GCB
3
-180 to 180°
[0°]
The phase angle compensation
corrects the degree between
generator voltage and busbar
voltage. The configured degree is
added to the real measured phase
angle.
Visible only, if parameter 8825 is
"On".
Notes
Ensure correct configuration to
prevent erroneous synchronization
settings to avoid generator
destructive power. Incorrect
wiring cannot be compensated for
with this parameter!
3432
Dead bus closure GCB
2
[On]
A dead busbar closure is allowed if
the required conditions are met.
Off
A GCB close command to a dead
busbar is prevented.
Synchronization is still possible.
Notes
This parameter only applies to
application modes
A03
and
A04
.
281
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.3 Configure Breakers: GCB
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...