ID
Parameter
CL
Setting range
[Default]
Description
5798
Point 2 Q/S rated
-0.99 to +0.99
[+0.31]
The value entered into "Point 2
Reactive power" defines the y-
coordinate of point 2
5032
Point 3 voltage
0.0 to 150.0%
[106.0%]
The value entered into "Point 3
Voltage" defines the x-coordinate
of point 3
5033
Point 3 Q/S rated
-0.99 to +0.99
[+0.31]
The value entered into "Point 3
Reactive power" defines the y-
coordinate of point 3
5034
Point 4 voltage
0.0 to 150.0%
[106.0%]
The value entered into "Point 4
Voltage" defines the x-coordinate
of point 4
5035
Point 4 Q/S rated
-0.99 to +0.99
[+0.31]
The value entered into "Point 4
Reactive power" defines the y-
coordinate of point 4
5799
Q(V) response time
001 to 999 s
[10 s]
The response with a new reactive
power setpoint acting on the
analog command variable "05.29
PF characteristic [%]" can be
delayed. Q(V) response time is
used to calculate the power factor
characteristic Q(V), parameter
Notes
The delay is realized with a PT-1
filter. Therefore the reaction times
are optimized for the range 10 s
until 60 s within a symmetrical
characteristic curve.
Accuracy of the setup Q(V)
response time is given within a
symmetrical characteristic curve.
5023
Q(V) Hysteresis
0 to 20%
[0%]
The hysteresis for the Q(V)
characteristic acts as a deadband
for the selected band. If the Mains
voltage is within the hysteresis
the resulting power factor
characteristic reference doesn't
change.
4.4.4.2.4
Reactive Power / Power Factor setpoint filter
Introduction
The FNN VDE-AR-N 4105 / 4110 requests a reactive power control with a setpoint which is
leaded over a PT1-element. The PT1-element shall be adjustable with a 3 tau setting. The
3 tau setting defines at what time shall be reached 95% of the original setpoint change.
This 3 tau value is configurable.
315
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.4 Reactive Power / Power Factor setpoint filter