6.2.1.2
Configuring Automatic Operation
⚙
1. ▷
Either on the front panel or using ToolKit navigate to menu [PARAMETER / Configuration /
Configure application / Configure operation modes / Operation mode AUTO].
2. ▷
Fig. 218:
LogicsManager function "Start req. in AUTO"
Configure the LogicsManager 86.90 function »12120 Start req. in AUTO« as shown in
(
) to start the generator in Automatic operating mode if discrete input [DI
02] ("09.02 Discrete input 2") is energized or a remote start request ("04.13 Remote
request" = start via interface) is issued.
6.2.1.3
Configuring Emergency Operation
Configure emergency operation to be initiated if the mains fails for at least 3 seconds or
the MCB cannot be closed.
⚙
1. ▷
Configure the parameters listed below.
ID
Parameter
Value
Comment
2802
Emergency
run
On
Emergency operation is enabled
2800
Mains fail
delay time
3.00 s
Emergency operation is initiated if the mains fail for a t
least 3 seconds
3408
Emerg.
start with
MCB failure
Yes
Emergency operation is initiated if the MCB fails to close
Table 98: Parameter configuration for emergency run
See
for further settings possibilities.
693
easYgen-3000XT Series
B37574
6 Application Field
6.2.1.2 Configuring Automatic Operation
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...