ID
Parameter
CL
Setting range
[Default]
Description
For information on the
LogicsManager and its default
settings see
.
12540
Start w/o load
(Start without assuming
load )
2
Determined by LogicsManager
86.19
[(0 & 1) & 1]
= 10718
If this LogicsManager condition is
TRUE switching from mains to
generator supply following an
engine start is prevented (the GCB
close operation is blocked).
This function may be used to
perform a test operation. If an
emergency power case occurs
meanwhile, it is still possible to
change to generator operation.
If this condition becomes TRUE in
islanded operation, the GCB
cannot be opened before the MCB
has been closed.
Notes
For information on the
LogicsManager and its default
settings see
.
4.4.5.3
Operation Mode TEST
Fig. 177:
TEST button
Operation mode TEST gives the opportunity to test the genset. It can be activated via HMI
button »TEST« or parameter 4672 »Test run mode«.
When the Test Run is time restricted:
• The remaining time is displayed on HMI.
•
• The device can change its operating mode after execution of the TEST mode.
•
In TEST mode the breakers are operated like in the application mode configured. The
handling in the setpoint screen is be the same like in the AUTOMATIC mode.
Emergency run (AMF) and sprinkler run -- if configured -- both are fully supported.
384
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.3 Operation Mode TEST
Released