Test without load
This is the LogicsManager function "Start w/o load" (parameter
). If the
conditions for this LogicsManager function are TRUE, the engine will provide an automatic
starting sequence and keep the generator running until this function is FALSE again.
Then the unit will perform an automatic stop sequence and remain in standby in auto
mode.
The message "Start w/o load" is displayed during the test without load. If the mains fails
during test without load and the emergency mode is enabled, the unit will take over the
load.
The unit will open the MCB and close the GCB. When the mains return, it will transfer the
load back to the mains according to the configured breaker transition mode after the
mains settling timer has expired. The engine will keep running until the conditions for
"Start w/o load" are FALSE again.
713
easYgen-3000XT Series
B37574
6 Application Field
6.3.5.2 Setting Up A Test With Or Without Load