ID
Parameter
CL
Setting range
[Default]
Description
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
3253
3259
Enabled
4
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
463
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.6.2.1 Generator Ground Fault (Level 1 & 2)
Released