“08.39 J1939 dev. 2 timeout”, “08.40 J1939 dev. 3 timeout or “08.77 J1939 AVR timeout
will be triggered.
ECU settings
ID
Parameter
CL
Setting range
[Default]
Description
15172
Monitoring
2
On
Monitoring of the ECU's CAN
messages is carried out according
to the following parameters. The
address of the ECU is taken from
parameter “Engine control
address” (
)
[Off]
Monitoring is disabled.
15176
Delay
2
0.02 to 999.00 s
[1.00 s]
The delay is configured with this
parameter. If the interface does
not receive a CAN message from
the ECU within this delay time, the
action specified by the alarm class
is initiated.
The delay timer is re-initialized if
any message from the ECU is
received.
15173
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned to an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
15174
Self acknowledge
2
[Yes]
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
No
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
15175
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
562
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.6 CAN Interface 2 - J1939 Interface
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...