Example 2: Power factor interface setpoint
The power factor setpoint value must be written to object 21FC (hex), i.e. parameter
508.
A power factor of 1 = 1000 (dec) = 03E8 (hex) is to be transmitted.
• Modbus address = 40000 + (Par. ID + 1) = 40509
•
• Modbus length = 1 (UNSIGNED 16)
•
⚙
ᐳ
To set the parameter address in ModScan32:
1. ▷
Fig. 295:
Modscan32 at address 40509
Analogous to
set the parameter address as shown in
☼
Example 3: Frequency interface setpoint
The frequency setpoint value must be written to object 21FD (hex), i.e. parameter 509.
A frequency value of 50.00 Hz = 5000 (dec) = 1388 (hex) is to be transmitted.
• Modbus address = 40000 + (Par. ID + 1) = 40510
•
• Modbus length = 1 (UNSIGNED 16)
•
⚙
ᐳ
To set the parameter address in ModScan32:
1. ▷
Fig. 296:
Modscan32 at address 40510
Analogous to
set the parameter address as shown in
797
easYgen-3000XT Series
B37574
6 Application Field
6.5.1.2 Setpoint Setting
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...