ID
Parameter
CL
Setting range
[Default]
Description
2
Cut-off-frequency = 0.16 Hz (filter
time constant = 1.0 s)
[3]
Cut-off-frequency = 0.08 Hz (filter
time constant = 2.0 s)
4
Cut-off-frequency = 0.04 Hz (filter
time constant = 4.0 s)
5
Cut-off-frequency = 0.02 Hz (filter
time constant = 8.0s)
1034
1084
1134
Unit
2
up to 6 characters text
[ _ _ _ _ _ _ ]
This parameter is assigning a unit
text to the displayed analog value.
Notes
This parameter may only be
configured using ToolKit.
If »°C« or »bar« is assigned the
unit will be converted into "F" or
"psi" automatically if the
corresponding parameter for
conversion
and/or
is configured to YES.
The max. number of characters is
39 but depends on numbers of
Bytes for each character. The
Bytes/character are defined by the
font of the currently selected
language.
Up to six characters are
best for display/HMI; more will
override screen border/frame.
Please verify the length on the
display for best view!
3632
3634
3636
Bargraph minimum
2
-21000000.00 to 21000000.00
[0.00]
The start value for the bar graph
display of the analog input is
defined here. The value must be
entered according to the display
format, which refers to the analog
input type (parameter
3633
3635
3637
Bargraph maximum
2
-21000000.00 to 21000000.00
[2000.00]
The end value for the bar graph
display of the analog input is
defined here. The value must be
entered according to the display
format, which refers to the analog
input type (parameter
Table 49: Analog Inputs 1 to 3 sender settings
4.4.2.5
Analog Outputs
4.4.2.5.1
Analog Outputs 1 and 2
The analog outputs AO 1 and AO 2 may either be configured as analog or PWM outputs.
The analog outputs are prepared for speed and voltage biasing signal for a speed
controller and voltage regulator.
250
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.5 Analog Outputs
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...