ID
Parameter
CL
Setting range
[Default]
Description
This parameter is only visible if
wire break monitoring (parameter
not set to "Off"
For additional information refer to
.
1005
1055
1105
Self acknowledge
wire break
2
Yes
The control automatically clears
the alarm if the fault condition is
no longer detected.
[No]
The control does not automatically
reset the alarm when the fault
condition is no longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
Notes
This parameter is only visible wire
break monitoring (parameter
) is not
set to "Off"
10113
10114
10116
Filter time constant
0/4 to 20 mA and 0 to
1 V
2
Off, 1 to 5
A low pass filter may be used to
reduce the fluctuation of an
analog input reading.
The cut-off-frequency is defined as
usual with 63% (e
-1
).
Off
The analog input is displayed
without filtering.
1
Cut-off-frequency = 7.96 Hz (filter
time constant = 0.02 s)
2
Cut-off-frequency = 3.98 Hz (filter
time constant = 0.04 s)
[3]
Cut-off-frequency = 1.99 Hz (filter
time constant = 0.08 s)
4
Cut-off-frequency = 0.99 Hz (filter
time constant = 0.16 s)
5
Cut-off-frequency = 0.50 Hz (filter
time constant = 0.32 s)
Filter time constant
for
0 to 2000 Ω
2
Off, 1 to 5
A low pass filter may be used to
reduce the fluctuation of an
analog input reading.
The cut-off-frequency is defined as
usual with 63% (e
-1
).
Off
Cut-off-frequency = 0.64 Hz (filter
time constant = 0.25 s)
1
Cut-off-frequency = 0.32 Hz (filter
time constant = 0.5 s)
249
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.4.2 Analog Inputs 1 to 3 (0 to 2000 Ω | 0/4 to 20 m A | 0 to 1 V)
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...