ID
Parameter
CL
Setting range
[Default]
Description
• EEM SISU: 0/(1)
•
• Cummins: 0
•
• ADEC ECU8/ECU9
•
MTU: 0
• Hatz EDC17: 0
•
• Standard: Please refer
•
to
and to the
manual of your J1939
ECU manufacturer.
Details may be found in the
manual of the genset
control and in
.
15108
Reset previous
act. DTCs - DM3
2
Yes
[No]
If this parameter is set to
"Yes", a DM3 message
"Acknowledge passive
faults" is sent. After that
this parameter is reset
automatically to "No".
As a result the alarms DTCs
(Diagnostic Trouble Codes)
of (DM2) which no longer
apply are cleared.
15133
Reset act. DTCs -
DM11
2
Yes
[No]
If this parameter is set to
"Yes", a DM11 message
"Acknowledge active
faults" is sent. After that
this parameter is reset
automatically to "No".
As a result the alarms DTCs
(Diagnostic Trouble Codes)
of (DM1) which no longer
apply are cleared.
15103
SPN version
2
Version 1 / Version 2 /
Version 3
[Version 1]
The J1939 protocol
provides 4 different
versions for the conversion
method of the Suspect
Parameter Number (SPN).
This is important for a
correct interpretation of the
alarm messages (DM1 &
DM2).
This parameter defines the
version of the conversion
method: Version 1,
632
easYgen-3000XT Series
B37574
4 Configuration
4.7.4.2.2 J1939 Interface
Released