ID
Parameter
CL
Setting range
[Default]
Description
engines, even if this does not
match the best possible efficiency.
If an engine selection yields a
condition, in which multiple small
engines with its rated power cover
exactly the rated power of an
possible bigger engine, the bigger
engine is preferred
Yes
The priority order considers the
engine size for the start of the
next engine for gensets with the
same priority.
[No]
The priority order does not
consider the rated power of the
engines to fit the best size of
engines.
5755
Fit service hours
2
With this parameter the LDSS
function can be configured to start
and stop redundant engines
according to their engine running
hours with different methods.
[Off]
The engine running hours are not
considered when evaluating the
engines to be started for gensets
with same priority. The parameter
»Changes of
engines« has no influence and can
be ignored.
Staggered
The remaining hours until the next
service is required are considered
when evaluating the engines to be
started for gensets with same
priority. The gensets are utilized in
a way that the maintenance may
be performed at different times to
ensure that not all gensets have a
downtime due to a maintenance
at the same time. The genset with
the lowest hours until the next
service will be started first.
Notes
To run this functionality properly
the maintenance call must be
acknowledged accordingly.
Equal
The remaining hours until the next
service is required are considered
when evaluating the engines to be
started for gensets with same
priority. The gensets are utilized in
a way that the maintenance may
be performed at the same time for
all gensets. The genset with the
highest hours until the next
service will be started first.
Notes
To run this functionality properly
the maintenance call must be
acknowledged accordingly.
400
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.5.3 Generator Selection
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...