Fig. 351:
Remote control - start/stop priority
shows the reaction of the command variable on the various status changes
of the bits.
The easYgen does not react on the disabling of the start bit, but only on the enabling of
the stop bit. This has the advantage that it is not required to maintain the connection
established for the whole time in case of a remote start via a modem.
Remote control word 2
Object 21F8h (Parameter 504)
This object is required for remote control. The data type is UNSIGNED16.
Bit 15 = 1
Bit 14 = 1
Bit 13 = 1
Bit 12 = 1
Bit 11 = 1
Bit 10 = 1
Bit 9 = 1
Bit 8 = 1
Bit 7 = 1
Request active power setpoint 2 – this bit activates the LogicsManager command variable
[04.40] "Remote power setpoint 2" and is dedicated for switching from active power
setpoint 1 to active power setpoint 2
Bit 6 = 1
Request power factor setpoint 2 – this bit activates the LogicsManager command variable
[04.39] "Remote PF setpoint 2" and is dedicated for switching from power factor setpoint 1
to power factor setpoint 2
Bit 5 = 1
Request frequency setpoint 2 – this bit activates the LogicsManager command variable
[04.38] "Remote frequency setpoint 2" and is dedicated for switching from frequency
setpoint 1 to frequency setpoint 2
1066
easYgen-3000XT Series
B37574
9 Appendix
9.2.9.1 Receive Data (sent from remote control to the easYgen)
Released