ID
Parameter
CL
Setting range
[Default]
Description
power will be distributed
proportionally among all
generators in relation to their
rated reactive power.
12905
Volt. droop act.
(Voltage droop active)
2
Determined by LogicsManager
86.26
[(08.17 Missing members OR
08.06 GCB fail to open08.06
GCB fail to open) & 1]
= 11605
If this LogicsManager condition is
TRUE, the voltage droop is
enabled.
Example
• Rated reactive power:
•
400 kvar
• Rated voltage setpoint: 410 V
•
• Droop 5.0%
•
• Reactive power 0 kvar = 0%
•
of rated power
• Voltage is adjusted to (410 V
•
– [5.0% * 0.0 * 410 V]) =
410 V.
• Reactive power 400 kvar =
•
100% of rated reactive power
• Voltage is adjusted to (410 V
•
– [5.0% * 1.0 * 410 V]) =
410 V – 20.5 V = 389.5 V.
Notes
For information on the
LogicsManager and its default
settings see
.
12938
Release V-control
2
Determined by LogicsManager
86.97
[(1 & 1) & 1]
= 11926
This LogicsManager is used to
activate generally the voltage
biasing to the sub controller. If the
LogicsManager is false the output
will be on the initial state (see
parameter
The LogicsManager condition
status 'TRUE' is activating the
voltage or reactive power
regulation according to the
LogicsManager 'V/Q control' ID
).
Notes
For information on the
LogicsManager and its default
settings see
.
6632
AVR J1939 Device
type
2
[Off]
AVR J1939 voltage setpoint is off.
Standard
Voltage setpoint for AVR is
transmitted via CAN J1939 SPN
3386 to the AVR.
5494
Volt. SP (J1939) max.
2
100.0 to 150.0%
[105.0%]
This parameter defines the scaling
between the result of "AM Volt. SP
PID-source [%]" and the
transmitted CAN voltage setpoint.
It defines the maximum deviation
of the setpoint from " 5602
Generator rated voltage". Where
302
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.1 Voltage Control
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...