Parameter
List of parameters
1-88
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the motor moment of inertia (without load).
Dependency:
IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
The parameter value is included, together with p0342, in the rated starting time of the motor.
Refer to: p0342
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
p0341 * p0342 + p1498 influence the speed/torque pre-control in encoderless operation.
Description:
Sets the ratio between the total moment of inertia/mass (load + motor) and the intrinsic motor moment of iner-
tia/mass (no load).
Dependency:
Refer to: p0341, p1498
Note:
p0341 * p0342 + p1498 influence the speed/torque pre-control in encoderless operation.
Description:
Sets the motor weight.
Dependency:
IEC drives (p0100 = 0): unit kg
NEMA drives (p0100 = 1): unit lb
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The parameter influences the thermal 3 mass model of the induction motor.
The parameter is not used for synchronous motors (p0300 = 2xx).
Description:
Sets the de-magnetizing time (for induction motors) after the inverter pulses have been canceled.
The inverter pulses cannot be switched in (enabled) within this delay time.
p0341[0...n]
Motor moment of inertia / Mot M_mom of inert
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
5042, 5210
P-Group:
Motor
Units group:
25_1
Unit selection:
p0100
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000000 [kgm²]
100000.000000 [kgm²]
0.000000 [kgm²]
p0342[0...n]
Ratio between the total and motor moment of inertia / Mot MomInert Ratio
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
5042, 5210
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1.000 10000.000
1.000
p0344[0...n]
Motor weight (for the thermal motor model) / Mot weight th mod
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(3), T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
27_1
Unit selection:
p0100
Not for motor type:
PEM, REL, FEM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [kg]
50000.0 [kg]
0.0 [kg]
p0347[0...n]
Motor de-excitation time / Mot t_de-excitat.
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
20.000 [s]
0.000 [s]