List of parameters
Parameter
1-207
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function gener-
ator.
Value:
0:
Cont. smoothing
1:
Discont smoothing
Dependency:
No effect up to initial rounding-off time (p1130) > 0 s.
Note:
p1134 = 0 (continuous smoothing)
If the setpoint is reduced while ramping-up, initially a final rounding-off is carried out and then the ramp-up com-
pleted. During the final rounding-off, the output of the ramp-function generator continues to go in the direction of the
previous setpoint (overshoot). After the final rounding-off has been completed, the output goes toward the new set-
point.
p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint.
For the setpoint change there is no rounding-off.
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note:
This time can be exceeded if the DC link voltage reaches its maximum value.
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1134[0...n]
Ramp-function generator rounding-off type / RFG round-off type
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
3070
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(1), U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3060, 3070
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
600.000 [s]
0.000 [s]
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3070
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3070
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
30.000 [s]