F01040
Save parameter settings and carry out a POWER ON
Message value:
-
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
A parameter was changed in the drive system which means that it is necessary to save the parameters and re-boot
(e.g. p0110).
Remedy:
- save the parameters (p0971/p0977).
- carry out a POWER ON (power off/on) for all components.
F01041
Parameter save necessary
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Defective or missing files were detected on the memory card when booting.
Fault value (r0949, decimal interpretation):
1: Source file cannot be opened.
2: Source file cannot be read.
3: Target directory cannot be set up.
4. Target file cannot be set up/opened.
5. Target file cannot be written to.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
- save the parameters.
- download the project again to the drive unit.
- update the firmware
- if required, replace the Control Unit and/or memory card card.
F01042
Parameter error during project download
Message value:
Parameter: %1, Index: %2, fault cause: %3
Drive object:
All objects
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
An error was detected when downloading a project using the commissioning software (e.g. incorrect parameter
value).
For the specified parameter, it was detected that dynamic limits were exceeded that may possibly depend on other
parameters.
Fault value (r0949, interpret hexadecimal):
ccbbaaaa hex
aaaa = Parameter
bb = Index
cc = fault cause
0: Parameter number illegal.
1: Parameter value cannot be changed.
2: Lower or upper value limit exceeded.
3: Sub-index incorrect.
4: No array, no sub-index.
5: Data type incorrect.
6: Setting not permitted (only resetting).
7: Descriptive element cannot be changed.
9: Descriptive data not available.
11: No master control.
15: No text array available.
17: Task cannot be executed due to operating state.
20: Illegal value.
21: Response too long.
22: Parameter address illegal.
23: Format illegal.