List of parameters
Parameter
1-41
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the smoothing time constant for the following display values:
SERVO: r0078[1], r0079[1], r0081 (calculated from the quantities smoothed with p0045), r0082[1].
VECTOR: r0063[1], r0068[1], r0080[1], r0082[1].
Description:
Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
Dependency:
Refer to: r0002
Note:
The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a "switching on inhibited".
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
p0045
Smoothing time constant, display values / T_smth display
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
4715, 5610,
5730, 6714, 8012
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
1000.00 [ms]
1.00 [ms]
r0046.0...31
CO/BO: Missing enable sig / Missing enable sig
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
2634
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
OFF1 enable missing
Yes
No
-
01
OFF2 enable missing
Yes
No
-
02
OFF3 enable missing
Yes
No
-
03
Operation enable missing
Yes
No
-
04
Armature short-circuit / DC braking, enable
missing
Yes
No
7014,
7016
05
STOP2 enable missing
Yes
No
-
06
STOP1 enable missing
Yes
No
-
08
EP terminals enable missing
Yes
No
-
09
Infeed enable missing
Yes
No
-
10
Ramp-function generator enable missing
Yes
No
-
11
Ramp-function generator start missing
Yes
No
-
12
Setpoint enable missing
Yes
No
-
16
OFF1 enable internal missing
Yes
No
-
17
OFF2 enable internal missing
Yes
No
-
18
OFF3 enable internal missing
Yes
No
-
19
Pulse enable internal missing
Yes
No
-
20
Armature short-circuit/DC braking internal
enable missing
Yes
No
7014,
7016
21
STOP2 enable internal missing
Yes
No
-
22
STOP1 enable internal missing
Yes
No
-
25
Function bypass active
Yes
No
-
26
Drive inactive or not operational
Yes
No
-
27
De-magnetizing not completed
Yes
No
-
28
Brake open missing
Yes
No
-
29
Cooling system ready signal missing
Yes
No
-
30
Speed controller inhibited
Yes
No
-
31
Jog setpoint active
Yes
No
-