Parameter
List of parameters
1-192
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Displays the selected and effective fixed speed setpoint.
This setpoint is the output value for the fixed speed setpoints and must be appropriately interconnected (e.g. with
the main setpoint).
Recommend.:
Interconnect the signal with main setpoint (p1070).
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1070, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
Description:
Sets the configuration for the motorized potentiometer.
Note:
Re bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p1040.
1: The setpoint for the motorized potentiometer is saved after OFF and after ON set to the saved value. In order to
save in a non-volatile fashion, bit 03 should be set to 1.
Re bit 01:
0: Without ramp-function generator in the automatic mode (ramp-up/ramp-down time = 0).
1: With ramp-function generator in the automatic mode.
For manual operation (0 signal via BI: p1041), the ramp-function generator is always active.
Re bit 02:
0: Without initial rounding-off
1: With initial rounding-off. The selected ramp-up/down time is correspondingly exceeded. The initial rounding-off is
a sensitive way of specifying small changes (progressive reaction when keys are pressed).
The jerk for the initial rounding-off is independent of the ramp-up time and only depends on the selected maximum
speed (p1082). It is calculated as follows:
r = 0.01 % * p1082 [1/s] / 0.13^2 [s^2]
The jerk acts up until the maximum acceleration is reached (a_max = p1082 [1/s] / p1047 [s]), and then the drive
continues to run linearly with a constant rate of acceleration. The higher the maximum acceleration (the lower that
p1047 is), the longer the ramp-up time increases with respect to the set ramp-up time.
r1024
CO: Fixed speed setpoint effective / n_set_fixed eff
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
1550, 3010
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1030[0...n]
Motorized potentiometer configuration / Mop configuration
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
DDS, p0180
Func. diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0000 0110 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Data save active
Yes
No
-
01
Automatic mode, ramp-function generator
active
Yes
No
-
02
Initial rounding-off active
Yes
No
-
03
Save in NVRAM active
Yes
No
-
04
Ramp-function generator always active
Yes
No
-