Parameter
List of parameters
1-324
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency:
Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117
Description:
Displays the first status word of faults and alarms.
Note:
Re bit 03, 05, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present"/"alarm present" has occurred, a change
in the buffer was also detected (r0944, r9744, r2121).
Re bit 06, 08:
These status bits are used for internal diagnostic purposes only.
Re bit 11, 12:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes
only on certain automation systems with integrated SINAMICS functionality.
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2155, r2197
Description:
Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency:
Refer to: p2142, r2199
14
External fault 2 (F07861) effective
Yes
No
-
15
External fault 3 (F07862) effective
Yes
No
-
r2139.0...12
CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
All objects
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1530, 2548
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Being acknowledged
Yes
No
-
01
Acknowledgment required
Yes
No
-
03
Fault present
Yes
No
-
05
Safety message present
Yes
No
-
06
Internal message 1 present
Yes
No
-
07
Alarm present
Yes
No
-
08
Internal message 2 present
Yes
No
-
11
Alarm class bit 0
High
Low
-
12
Alarm class bit 1
High
Low
-
p2140[0...n]
Hysteresis speed 2 / n_hysteresis 2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
300.00 [rpm]
90.00 [rpm]
p2141[0...n]
Speed threshold 1 / n_thresh val 1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
5.00 [rpm]