Parameter
List of parameters
1-580
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the velocity tolerance limit for the "SAM" function.
SAM is de-activated once the set velocity limit has been undershot.
Note:
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
For p9568 = p9368 = 0, the following applies:
The value in p9546/p9346 (SSM) is applied as the velocity limit for SAM.
Description:
Setting to select and de-select the acceptance test mode.
Value:
0:
[00 hex] De-select the acceptance test mode
172:
[AC hex] Select the acceptance test mode
Dependency:
Refer to: p9558, r9571, p9601
Refer to: C01799
Note:
Acceptance test mode can only be selected if the motion monitoring functions, which are integrated in the drives,
are enabled (p9601.2/p9801.2).
Description:
Displays the status of the acceptance test mode.
Value:
0:
[00 hex] Acc_mode inactive
12:
[0C hex] Acc_mode not possible due to POWER ON fault
13:
[0D hex] Acc_mode not possible due to incorrect ID in p9570
15:
[0F hex] Acc_mode not possible due to expired Acc_timer
172:
[AC hex] Acc_mode active
Dependency:
Refer to: p9558, p9570
Refer to: C01799
p9568
SI Motion SAM velocity limit (processor 1) / SI Mtn SAM v_limP1
SERVO_S110-CAN
(Safety rot),
SERVO_S110-DP
(Safety rot),
SERVO_S110-PN
(Safety rot)
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
1000.00 [rpm]
0.00 [rpm]
p9570
SI Motion acceptance test mode (processor 1) / SI Mtn Acc_mode
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
00AC hex
0000 hex
r9571
SI Motion acceptance test status (processor 1) / SI Mtn acc_status
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
00AC hex
-