List of parameters
Parameter
1-259
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the signal source to change over the torque limits between variable and fixed torque limit.
1 signal from BI: p1551:
The variable torque limit applies (fixed torque limit + scaling).
0 signal from BI: p1551:
The fixed torque limit applies.
Example:
In order that for a Quick Stop (OFF3) the fixed torque limit is effective, BI: p1551 must be interconnected to r0899.5.
Description:
Sets the signal source for the scaling of the upper torque limiting to limit the speed controller output without taking
into account the current and power limits.
Notice:
Speed controller limiting is only active if a BICO interconnection is set for connector input p1552 or p1554, (different
than the factory setting).
Description:
Sets the signal source for the scaling of the lower torque limiting to limit the speed controller output without taking
into account the current and power limits.
Notice:
Speed controller limiting is only active if a BICO interconnection is set for connector input p1552 or p1554, (different
than the factory setting).
Description:
Sets the signal source for supplementary torque 3.
Notice:
The signal input is after the torque limit (r1538, r1539). For vector drives, the signals that are entered are only lim-
ited by the current and power limits.
Note:
The signal input is preferably used to enter the friction characteristic. The friction compensation is also effective if
the speed controller output reaches its torque limits, but the current limits have still not been reached (this only
applies to vector drives).
p1551[0...n]
BI: Torque limit variable/fixed signal source / M_lim var/fixS_src
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
5620, 5630,
6060, 6630
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p1552[0...n]
CI: Torque limit upper scaling without offset / M_max up w/o offs
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
5060
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
1
p1554[0...n]
CI: Torque limit lower scaling without offset / M_max low w/o offs
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
5060
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
1
p1569[0...n]
CI: Supplementary torque 3 / M_suppl 3
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
7010
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
p2003
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS S110
Страница 1: ...s SINAMICS S110 List Manual 06 2012 SINAMICS ...
Страница 2: ......
Страница 1272: ...List of abbreviations B 1272 Siemens AG 2012 All Rights Reserved SINAMICS S110 List Manual LH7 06 2012 6SL3097 4AP10 0BP3 ...
Страница 1286: ...Index C 1286 Siemens AG 2012 All Rights Reserved SINAMICS S110 List Manual LH7 06 2012 6SL3097 4AP10 0BP3 ...
Страница 1287: ......