Parameter
List of parameters
1-194
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the minimum speed/velocity for the motorized potentiometer.
Note:
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description:
Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency:
Refer to: p1037, p1038
Note:
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has
been powered up.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the set-
point must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
p1038[0...n]
Motorized potentiometer minimum speed / MotP n_min
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3020
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1039[0...n]
BI: Motorized potentiometer inversion / MotP inv
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1040[0...n]
Motorized potentiometer starting value / Mop start value
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3020
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1041[0...n]
BI: Motorized potentiometer manual/automatic / Mop manual/auto
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS S110
Страница 1: ...s SINAMICS S110 List Manual 06 2012 SINAMICS ...
Страница 2: ......
Страница 1272: ...List of abbreviations B 1272 Siemens AG 2012 All Rights Reserved SINAMICS S110 List Manual LH7 06 2012 6SL3097 4AP10 0BP3 ...
Страница 1286: ...Index C 1286 Siemens AG 2012 All Rights Reserved SINAMICS S110 List Manual LH7 06 2012 6SL3097 4AP10 0BP3 ...
Страница 1287: ......