Parameter
List of parameters
1-78
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency:
The number of pole pairs (r0313) is automatically re-calculated when the parameter is changed (together with
p0311), if p0314 = 0.
If p0310 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also asso-
ciated with quick commissioning, is pre-assigned accordingly.
Refer to: p0311, r0313, p0314
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Notice:
If p0310 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010
= 3).
Note:
For synchronous motors, the parameter is not required and must therefore be pre-assigned zero. For p0310 = 0, it
is not possible to calculate the pole pair; instead, it must be entered in p0314.
Description:
Sets the rated motor speed (rating plate).
Dependency:
If p0311 is changed and for p0314 = 0, the pole pair (r0313) is re-calculated automatically.
Refer to: p0310, r0313, p0314
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Notice:
If p0311 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010
= 3).
Description:
Sets the rated motor torque (rating plate).
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Description:
Displays the number of motor pole pairs. The value is used for internal calculations.
r0313 = 1: 2-pole motor
r0313 = 2: 4-pole motor, etc.
Dependency:
For p0314 > 0, the entered value is displayed in r0313.
For p0314 = 0, the pole pair number (r0313) is automatically calculated from the rated frequency (p0310) and the
rated speed (p0311).
Refer to: p0310, p0311, p0314
p0311[0...n]
Rated motor speed / Mot n_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [rpm]
210000.0 [rpm]
0.0 [rpm]
p0312[0...n]
Rated motor torque / Mot M_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(3)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
7_4
Unit selection:
p0100
Not for motor type:
ASM, REL, FEM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Nm]
1000000.00 [Nm]
0.00 [Nm]
r0313[0...n]
Motor pole pair number, actual (or calculated) / Mot PolePairNo act
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
MDS, p0130
Func. diagram:
5300
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory