List of parameters
Parameter
1-389
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency:
If there is no reference cam (p2607 = 0), the search for reference immediately starts with the axis traversing to the
zero mark.
Refer to: p2595, p2597, p2604, p2607, p2609, p2610
Caution:
If the reference cam is not adjusted so that at each search for reference the same zero mark for synchronization is
detected, then an "incorrect" axis reference point is obtained.
After the reference cam has been left, the search for the zero mark is activated with a time delay due to internal fac-
tors. This is the reason that the reference cam should be adjusted in this center between two zero marks and the
approach velocity should be adapted to the distance between two zero marks.
Note:
The velocity override is not effective when traversing to the zero mark.
Description:
Sets the maximum distance after leaving the reference cam when traversing to the zero mark.
Dependency:
Refer to: p2595, p2597, p2604, p2607, p2608, p2610
Refer to: F07459
Description:
Sets the tolerance bandwidth for the distance to the zero mark
The zero mark is evaluated within the maximum distance between the reference cam and zero mark (p2609) minus
the tolerance bandwidth for the distance to the zero mark (p2610).
Dependency:
Refer to: p2609
Description:
Sets the approach velocity after detecting the zero mark to approach the reference point.
Dependency:
Refer to: p2595, p2597, p2604, p2607, p2609, p2610
Note:
When traversing to the reference point, the velocity override is not effective.
p2609
EPOS search for reference, max. distance ref. cam and zero mark / Max s ref_cam ZM
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
3612
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [LU]
2147482647 [LU]
20000 [LU]
p2610
EPOS search for ref., tol. bandwidth for distance to zero mark / Tol_band to ZM
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
3612
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [LU]
2147482647 [LU]
2147482647 [LU]
p2611
EPOS search for reference, approach velocity, reference point / v_appr ref_pt
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
3612
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 [1000 LU/min]
40000000 [1000 LU/min]
300 [1000 LU/min]